Description
This powerpoint presentation outlines topics that include: summarize the proposed changes to theLead and Copper Rule;Simultaneous Compliance Considerations; Simultaneous Compliance Examples;Trends Related to Lead Corrosion Controland Simultaneous Compliance; and, Recent Examples Related to Lead CorrosionControl and Simultaneous Compliance. Conclusions were that:Recent Lead Detections and Investigations inWashington DC, Durham NC and other LocationsReveal Simultaneous Compliance Issues with theDBPR and Lead and Copper Rule;Recently Developed Materials such as the MDBPSimultaneous Compliance Guidance ManualShould be Consulted before Making anySignificant Process Changes;Changes in oxidant/disinfectant and coagulantCl:SO4 ratio have been found to impact leadcorrosion significantly, past guidance on leadcorrosion showed impacts of pH, inhibitors suchas phosphates and silicates, hardness, alkalinity,total dissolved solids, bio-corrosion, etc.;Proposed Changes to the Lead and Copper RuleSeek to Help Address Recent Trends by measuressuch aspreventing water systems above the lead actionlevel from remaining on a reduced schedule basedon maintaining Water Quality parameters, andrequiring water systems to provide advancednotice to the primacy agency of intended changesin treatment or source water that could increasecorrosion of lead; and,make only one major process change at a time andevaluate corrosion control before and after eachchange.
Product Details
- Edition:
- Vol. – No.
- Published:
- 06/01/2007
- Number of Pages:
- 14
- File Size:
- 1 file , 1.2 MB
- Note:
- This product is unavailable in Ukraine, Russia, Belarus