Description
Experiments were carried out to confirm the presence of chlorate ion (ClO3-) in the treated water of utilities that use hypochlorination. Sixteen commercially produced, concentrated liquid hypochlorite feedstocks were analyzed for ClO3-, and levels as high as 158 g percent ClO3- relative to hypochlorite ion were measured. Finished-water samples from the utilities surveyed contained as much as 0.30 mg ClO3-/L, primarily the result of decomposition of the liquid hypochlorite feedstocks. Although both dilution and lower temperatures can be effective in minimizing ClO3- formation, it was observed that diluting the initial liquid hypochlorite concentration by a factor of 2 is more effective than decreasing the temperature from 24 to 10C. A methodology is proposed that predicts the dilution or temperature reduction (or both) required to avoid significant ClO3- formation in the feedstock solutions. Includes 27 references, tables, figures.
Product Details
- Edition:
- Vol. 85 – No. 9
- Published:
- 09/01/1993
- Number of Pages:
- 9
- File Size:
- 1 file , 1.5 MB
- Note:
- This product is unavailable in Ukraine, Russia, Belarus